Monitors 4 PROFIBUS networks + ProfiTrace 2 streaming + OPC

The Head Station is the primary element of ComBricks and has to be inserted in the most left slot of the fixed backplane socket. It schedules the interaction between all modules and provides data storage and an Ethernet interface for the user.

Type 1A is the basic model and ALL Head Stations are hardware technically identical with type 1A.

Type 1B and 1C are enhanced types that contain a ProfiTrace core and advanced web server for permanent remote maintenance of the PROFIBUS installation over Ethernet (hardware is identical to type 1A).

  • Type 1A: NO monitoring capabilities, no streaming, no OPC
  • Type 1B: Monitors 1 PROFIBUS network + ProfiTrace 2 streaming + OPC
  • Type 1C: Monitors 4 PROFIBUS networks + ProfiTrace 2 streaming + OPC

For monitoring repeater modules or slave modules are required to provide PROFIBUS telegrams on the backplane network.

Product Information

Distinctive features
• Drives 32 modules (10 high-speed modules)
• Wide range of modules available
• Hot swap and extendible
• Powerful web server
• ProfiTrace OE for monitoring 4 networks
• Multi-language
• DIN-rail mounting
• IP 20

Your benefits
• Remote monitoring of your installation
• Easy to use
• The only product with an integrated oscilloscope for permanent PROFIBUS control over Ethernet
  • Remote maintenance station with ProfiTrace OE
  • Modular repeater backbone with hot swap
  • Transparent data hub (repeaters, fibre optic, RS-485-IS, DP slave, PROFINET, etc.)

Type differences (Hardware is identical with all types)

Head Station 1A

No ProfiTrace OE

Head Station 1B

ProfiTrace OE for 1 PROFIBUS network +

ProfiTrace 2 live streaming + OPC  (since June 2013)

Head Station 1C

ProfiTrace OE for 4 PROFIBUS networks +
ProfiTrace 2 live streaming + OPC

For all Head Stations

CommDTM

Backplane

Modules

32 (10 repeater modules positioned in the first 10 slots)

Currently available for the backplane

2.5 A

PROFIBUS networks

4

Compatible backplane units

101-200012, 101-200023, 101-200024, 101-200027

Power supply specifications

Power supply operating voltage range

12 to 24 VDC (tolerance range 11 to 26 VDC)

Do not connect, if the power on the backplane is supplied by a PWR-6A module.

Typical own Current consumption

73 mA at 24 VDC (externally powered)

230 mA at 5.72 VDC (externally or PWR-6A module powered)

Max. Current consumption

800 mA at 24 VDC (current consumption of other modules included)

Power dissipation

Max. 1.32 W (own power dissipation)

Max. 20W (power dissipation of other modules included) 

Reverse polarity protection

 

Yes

Redundant power supply

Yes

Wire diameter

< 2.5 mm2

Installation notes:

The device shall be supplied from an isolating transformer having a secondary Listed fuse rated either:

  • Maximum 5 amps for voltages 12 to 20 V, or
  • Maximum 4 amps for voltages 21 to 24 V,

    or is supplied by a Class 2 power supply or equivalent.

Ethernet

Connector

RJ-45

Cable length

Max. 100 m

Link speed

10 / 100 Mbps

MAC address

9C.B2.06.xx.xx.xx (label on the side of the Head Station)

Supported protocols

HTTP, FTP, SMTP, TELNET, DHCP, SNMP

Default IP address after reset/purchase

192.168.1.254

Connections

20 simultaneous web server clients

Relay contact

Resistance

300 mOhm (plug included)

Voltage

24 VAC

Current

0.5 A

Installation notes:

The Relay output shall be supplied from an isolating transformer having a secondary Listed fuse rated either:

  • Maximum 5 amps for voltages 12 .. 20 V, or
  • Maximum 4 amps for voltages 21 .. 24 V,

or is supplied by a Class 2 power supply or equivalent.

SD Card

Types

SD and SDHC

Size

Max. 32 GB (1 GB is provided)

Connector Layout

Power supply

Plug-able screw connector, pitch 5,08 mm

Pin – :  0 V
Pin +:  24 VDC

Pin SH: Shield

SH connected internally to DIN-rail with spring-loaded contact 

Alarm contact

Pin 1: NO
Pin 2: NO

potential-free relay contact, normally open

Others

Weight

150 g

MTBF

2873918 hours, at 30o Celsius, IEC TR 62380

Standards and approvals

CE

EMC Directive 2014/30/EU, class A Digital Device

RoHS Directive 2011/65/EU

FCC

47 CFR 15, Unintentional Radiator, class A Digital Device.

UL

Report reference: E468970

Standards for safety: UL 508 – Industrial Control Equipment CSA C22.2 No. 142-M1987 – Industrial Control Equipment

Order Codes   101-20011C
Included Components Anybus ComBricks Head station
Warranty  1 year

Book your product

We are fully committed to providing our customers with the very best products and customer service. We believe in going the extra mile to ensure that each customer is satisfied with our products and solutions. We have the experience and the reputation in the field to deliver the products customers need to expedite their projects and assure quality every step of the way.

Our expertise lies in establishing, maintaining, and leveraging plant data for business benefit. Through our innovative solutions, we work alongside you to streamline processes, enhance efficiency, and reduce costly downtime.

Copyright @2024 Industrial Data Xchange.
All rights reserved.

CONTACT US

Main: +27 (11) 548 9960
Sales: +27 (11) 548 9970

SOCIAL MEDIA