Connect non-networked industrial devices and equipment to PROFINET-IRT
Integrate your serial RS-232/422/485 based industrial devices and equipment to a PROFINET-IRT control system without the need for any changes to the device. Just connect, configure and you’re done!
The Anybus Communicator is a proven and trusted protocol converter gateway that connects non-networked industrial devices and equipment to PROFINET-IRT. The gateway performs intelligent protocol conversion and presents the serial data to the Master PLC/Controller as easily processed I/O data.
The Communicator is a slim stand-alone gateway designed for IP20 and DIN-rail mounting, requiring a 24-volt power supply. The Communicator is conformance tested to current PROFINET-IRT specifications guaranteeing network compatibility.
Convert almost any type of serial protocol
The Communicator is capable of converting almost any type of serial protocol such as Modbus RTU, ASCII, DF1, or any other type of proprietary Query/Response or Produce/Consume protocol.
Typical serial applications
Typical serial applications include variable frequency drives, sensors, actuators, human-machine interfaces, barcode readers, RFID readers, and industrial scales among others.
Product Information
- Features and benefits
- Serial features
- PROFINET IRT features
- Technical specifications
- Datasheet
- In the box
- Convert almost any RS-232/422/485 Request/Response or Produce/Consume protocol in just a few minutes — For example Modbus RTU, ASCII, DF1.
- Pre-defined for Modbus RTU. Avoid the hassle of scripting and serial Modbus frame building with the 6-step Modbus RTU wizard.
- No hardware or software changes are required for the connected automation device
- Compatible with PLCs from leading manufacturers such as Siemens, Rockwell, Schneider Electric, etc
- Complete protocol conversion performed by the Communicator, no PLC function blocks required
- Handy Save/Load function means a completed configuration can be re-used for many other installations
- Included “Anybus Configuration Manager” with flexible serial frame building capabilities
- Versions with Dual Port switched Ethernet allows for daisy-chaining and eliminates the need for external switches
- Global free technical support and consultancy
No high-level programming skills are needed to set up the Anybus® Communicator as the configuration is accomplished using the included, easy to use Windows™ based ACM (Anybus Configuration Manager).
- Selectable RS-232/422/485 interface
- Pre-defined 6-step Modbus-RTU configuration wizard
- Selectable pre-loaded DF1 commands. No scripting or serial frame building required!
- Ability to configure ASCII or vendor-specific protocols (Request/Response or Produce/Consume via a visual frame building interface
- Multi-language support for English, German, Spanish, Italian, French, Polish, Russian, Chinese, and Japanese
- Handy Save/Load function allows for a completed configuration to be re-used for many other installations
- Password protection prevents unauthorised upload and download of configurations
- Serial Line Listener and In-built Checksum calculations for diagnostic and troubleshooting
- Complete PROFINET RT and IRT functionality specification 2.3
- Conformance tested supporting Class A, B, and C
- Max 220 bytes of Input and 220 bytes of Output data
- Baud rate 10/100 Mbit/s
- Isochronous cycle times 0.25 to 4 ms (25 Us increments)
- SNMP-MIBII support
- TCP/IP Configuration via DCP (Discovery and Configuration Protocol)
- LLDP (Linked Layer Discovery Protocol)
- Support for I&M (Identification & Maintenance)
- PROFINET uplink configuration via .GSDML file
- Dual-port cut-through switch
- Dual RJ-45 ports available simultaneously
- PROFINET Asset Management
Communicator RS-232/422/485
Protocol | Configurable RS-232/422/485 based produce/consume, query/response ASCII |
Max stations | 31 (with RS485/422) |
Baud rate | 1,2-57,6 kbit/s |
Physical standards | RS232/422/485 |
Modbus Commands | 0x01 Read Coils, 0x02 Read Discrete Inputs, 0x03 Read Holding Registers, 0x04 Read Input Registers, 0x05 Write Single Coil, 0x06 Write Single Register, 0x07 Read Exception Status, 0x08 Diagnostics, 0x0B Get Comm Event Ctr, 0x0C Get Comm Event Log, 0x0F Write Multiple Coils, 0x10 Write Multiple Registers, 0x11 Report Slave ID, 0x14 Read File Record, 0x15 Write File Record, 0x16 Mask Write Register, 0x17 Read/Write Multiple Registers, 0x18 Read FIFO Queue Customized commands can be created (in the Anybus Configuration Manager) |
DF1 Services | 0x01 Integrity Check, 0x02 Read Diagnostics, 0x03 Read Data, 0x04 Write Data Customized services can be created (in the Anybus Configuration Manager) Technical Details Standard |
Technical details
Dimensions (L x W x H) with the serial and power connector | 120 x 75 x 27 mm 4,72 x 2,95 x 1,06” |
|
Weight | 150 grams, 0.33 lb | |
Protection class | IP20 Nema rating 1 | |
Enclosure material | l PC ABS, UL 94 | |
Installation position | Any | |
Mounting | DIN rail (35 * 7,5/15) | EN50022 |
Certifications
UL | File Number: E203225 | UL 508 Ind. Cont. Eq. |
Hazardous Locations | CLASS 1, DIVISION 2, GROUPS A, B, C, AND D, T4 | ISA 12.12.01 |
CE | 2004/108/EC | EN 61000-6-4 EN 61000-6-2 |
Electrical characteristics
Power | 24 VDC +/- 10 % |
Current consumption | Max 300 mA, Typical 100 mA |
Environmental characteristics
Reverse voltage protection | Yes | |
Short circuit protection | Yes | |
Galvanic isolation on the subnetwork | Yes | EN 60950-1 |
MTTF | >550 000 h | Telcordia Issue 2, Method 1 Case 3 at 30 o C |
Hardware characteristics
Operating temp | 0 to 55 o C, 32 to 131 o F |
Storage temp | -40 to 85 o C, -40 to 185 o F |
Relative Humidity | 0-95% non condensing |
Installation altitude | up to 2 000 m |
Immunity and emission for the industrial environment
Electrostatic discharge | +/- 4 kV | EN 61000-4-2 |
Electromagnetic RF fields | 10 V/m 80 MHz – 1 GHz 3 V/m 1,4 GHz – 2,0 GHz 1 V/m 2,0 GHz – 2,7 GHz |
EN 61000-4-3 |
Fast Transients | +/- 1 kV | EN 61000-4-4 |
Surge protection | +/- 1 kV | EN 61000-4-5 |
RF conducted interference | 10 V/rms | EN 61000-4-6 |
Emission (at 10 m) | 40 dB 30 MHz – 230 MHz 47 dB 30 MHz – 1 GHz |
CISPR 16-2-3 |
Order Code: AB7078
Included Components:
- Quickstart documentation
- Configuration cable (RS-232)
- D-sub connector with screw terminals for serial sub-network
- Configuration software available for download
- (Power supply not included)
Optional Accessories:
- USB-RS-232 configuration adapter (Order Code: 019570)
Guarantee: 3 years
Book your product
We are fully committed to providing our customers with the very best products and customer service. We believe in going the extra mile to ensure that each customer is satisfied with our products and solutions. We have the experience and the reputation in the field to deliver the products customers need to expedite their projects and assure quality every step of the way.
Our expertise lies in establishing, maintaining, and leveraging plant data for business benefit. Through our innovative solutions, we work alongside you to streamline processes, enhance efficiency, and reduce costly downtime.
CONTACT US
Main: +27 (11) 548 9960
Sales: +27 (11) 548 9970
SOCIAL MEDIA
Copyright @2024 Industrial Data Xchange. All rights reserved.