Select Page

Connect non-networked industrial devices and equipment on a Modbus RTU network to Lonworks

Integrate your Modbus serial RS-232/422/485 based industrial devices and equipment to a LONWORKS control system without the need for any changes to the device. Just connect, configure and you’re done!

The Anybus Communicator is a proven and trusted protocol converter gateway that connects non-networked industrial devices and equipment on a Modbus RTU network to Lonworks.

The Communicator is a slim stand-alone gateway designed for IP20 and DIN-rail mounting, requiring a 24-volt power supply. The Communicator is conformance tested to current Lonworks specifications guaranteeing network compatibility.

Convert classic Modbus registers for I/O data

The gateway makes it possible to convert Modbus registers data to LonWorks Variables (SNVT‟s and/or UNVT‟s). You can create a set of variables according to LonMark functional Profiles or you can create your own set of variables with User-defined Network Variables (UNVT‟s).

The Communicator is a slave on the Modbus RTU side. This means that you connect this to a Modbus network which has a Modbus RTU Master connected. The configuration requires no programming and is made by an included configuration tool in the Windows environment.

Product Information

  • Convert almost any RS-232/422/485 Request/Response or Produce/Consume protocol in just a few minutes — For example Modbus RTU, ASCII, DF1.
  • Pre-defined for Modbus RTU. Avoid the hassle of scripting and serial Modbus frame building with the 6-step Modbus RTU wizard.
  • No hardware or software changes are required for the connected automation device
  • Compatible with PLCs from leading manufacturers such as Siemens, Rockwell, Schneider Electric, etc
  • Complete protocol conversion performed by the Communicator, no PLC function blocks required
  • Handy Save/Load function means a completed configuration can be re-used for many other installations
  • Included “Anybus Configuration Manager” with flexible serial frame building capabilities
  • Versions with Dual Port switched Ethernet allows for daisy-chaining and eliminates the need for external switches
  • Global free technical support and consultancy

No high-level programming skills are needed to set up the Anybus® Communicator as the configuration is accomplished using the included, easy to use Windows™ based ACM (Anybus Configuration Manager).

  • Selectable RS-232/422/485 interface
  • Pre-defined 6-step Modbus-RTU configuration wizard
  • Selectable pre-loaded DF1 commands. No scripting or serial frame building required!
  • Ability to configure ASCII or vendor-specific protocols (Request/Response or Produce/Consume via a visual frame building interface 
  • Multi-language support for English, German, Spanish, Italian, French, Polish, Russian, Chinese, and Japanese
  • Handy Save/Load function allows for a completed configuration to be re-used for many other installations
  • Password protection prevents unauthorised upload and download of configurations
  • Serial Line Listener and In-built Checksum calculations for diagnostic and troubleshooting
  • Certified for Lonmark application layer guidelines V3.2
  • Lonworks network variables and configuration of the gateway is made via the included configuration tool (network commissioning requires 3rd part tools)
  • Lonworks FT-X1 Transceiver
  • Up to 256 input + 256 output LonWorks Network Variables / Modbus Word Registers
  • Amount and type of network variables configurable, data linking between Lonworks variables (SNVT’s) and Modbus Registers
  • Lonworks baudrate 78 kbit/s
  • 1x D-sub 9-pin male RS-232 configuration port 
  • 1x 5-pin, 5.08 Phoenix network connector

Communicator RS-232/422/485

Protocol Configurable RS-232/422/485 based produce/consume, query/response ASCII
Max stations 31 (with RS485/422)
Baud rate 1,2-57,6 kbit/s
Physical standards RS232/422/485
Modbus Commands 0x01 Read Coils, 0x02 Read Discrete Inputs, 0x03 Read Holding Registers, 0x04 Read Input Registers, 0x05 Write Single Coil, 0x06 Write Single Register, 0x07 Read Exception Status, 0x08 Diagnostics, 0x0B Get Comm Event Ctr, 0x0C Get Comm Event Log, 0x0F Write Multiple Coils, 0x10 Write Multiple Registers, 0x11 Report Slave ID, 0x14 Read File Record, 0x15 Write File Record, 0x16 Mask Write Register, 0x17 Read/Write Multiple Registers, 0x18 Read FIFO Queue Customized commands can be created (in the Anybus Configuration Manager)
 DF1 Services 0x01 Integrity Check, 0x02 Read Diagnostics, 0x03 Read Data, 0x04 Write Data Customized services can be created (in the Anybus Configuration Manager) Technical Details Standard

Technical details

Dimensions (L x W x H) with the serial and power connector 120 x 75 x 27 mm
4,72 x 2,95  x 1,06”
Weight 150 grams, 0.33 lb
Protection class IP20 Nema rating 1
Enclosure material l PC ABS, UL 94
Installation position Any
Mounting DIN rail (35 * 7,5/15) EN50022

Certifications

UL File Number: E203225 UL 508 Ind. Cont. Eq.
Hazardous Locations CLASS 1, DIVISION 2, GROUPS A, B, C, AND D, T4 ISA 12.12.01
CE 2004/108/EC EN 61000-6-4
EN 61000-6-2

Electrical characteristics

Power 24 VDC +/- 10 %
Current consumption Max 300 mA, Typical 100 mA

Environmental characteristics

Reverse voltage protection Yes
Short circuit protection Yes
Galvanic isolation on the subnetwork Yes EN 60950-1
MTTF >550 000 h Telcordia Issue 2, Method 1 Case 3 at 30 o C

Hardware characteristics

Operating temp 0 to 55 o C, 32 to 131 o F
Storage temp -40 to 85 o C, -40 to 185 o F
Relative Humidity 0-95% non condensing
Installation altitude up to 2 000 m

Immunity and emission for the industrial environment

Electrostatic discharge +/- 4 kV EN 61000-4-2
Electromagnetic RF fields 10 V/m 80 MHz – 1 GHz
3 V/m 1,4 GHz – 2,0 GHz
1 V/m 2,0 GHz – 2,7 GHz
EN 61000-4-3
Fast Transients  +/- 1 kV EN 61000-4-4
Surge protection +/- 1 kV EN 61000-4-5
RF conducted interference 10 V/rms EN 61000-4-6
Emission (at 10 m) 40 dB 30 MHz – 230 MHz
47 dB 30 MHz – 1 GHz
CISPR 16-2-3

Order Code: AB7009

Included Components:

  • Quickstart documentation
  • Configuration program LWTool
  • D-sub connector with screw terminals for serial sub-network
  • Configuration software available for download
  • (Power supply not included)

Optional Accessories:

  • USB-RS-232 configuration adapter (Order Code: 019570)

Guarantee:  3 years

Book your product

We are fully committed to providing our customers with the very best products and customer service. We believe in going the extra mile to ensure that each customer is satisfied with our products and solutions. We have the experience and the reputation in the field to deliver the products customers need to expedite their projects and assure quality every step of the way.

Our expertise lies in establishing, maintaining, and leveraging plant data for business benefit. Through our innovative solutions, we work alongside you to streamline processes, enhance efficiency, and reduce costly downtime.

Copyright @2024 Industrial Data Xchange.
All rights reserved.

CONTACT US

Main: +27 (11) 548 9960
Sales: +27 (11) 548 9970

SOCIAL MEDIA


Fatal error: Uncaught Error: Call to undefined method WP_Error::save() in C:\XAMPP\htdocs\wp-content\plugins\complianz-gdpr\functions.php:1873 Stack trace: #0 C:\XAMPP\htdocs\wp-content\plugins\complianz-gdpr\functions.php(1798): cmplz_create_webp('C:\\XAMPP\\htdocs...', 'https://www.idx...') #1 C:\XAMPP\htdocs\wp-content\plugins\complianz-gdpr\integrations\services\youtube.php(83): cmplz_download_to_site('https://img.you...', 'youtubeU0su379_...') #2 C:\XAMPP\htdocs\wp-includes\class-wp-hook.php(324): cmplz_youtube_placeholder('https://img.you...', 'https://www.you...') #3 C:\XAMPP\htdocs\wp-includes\plugin.php(205): WP_Hook->apply_filters('https://www.idx...', Array) #4 C:\XAMPP\htdocs\wp-content\plugins\complianz-gdpr\functions.php(1717): apply_filters('cmplz_placehold...', 'https://www.idx...', 'https://www.you...') #5 C:\XAMPP\htdocs\wp-content\plugins\complianz-gdpr\class-cookie-blocker.php(613): cmplz_placeholder('youtube', 'https://www.you...') #6 C:\XAMPP\htdocs\wp-content\plugins\complianz-gdpr\class-cookie-blocker.php(404): cmplz_cookie_blocker->replace_tags('<!DOCTYPE html>...') #7 [internal function]: cmplz_cookie_blocker->filter_buffer('<!DOCTYPE html>...', 9) #8 C:\XAMPP\htdocs\wp-includes\functions.php(5464): ob_end_flush() #9 C:\XAMPP\htdocs\wp-includes\class-wp-hook.php(324): wp_ob_end_flush_all('') #10 C:\XAMPP\htdocs\wp-includes\class-wp-hook.php(348): WP_Hook->apply_filters('', Array) #11 C:\XAMPP\htdocs\wp-includes\plugin.php(517): WP_Hook->do_action(Array) #12 C:\XAMPP\htdocs\wp-includes\load.php(1279): do_action('shutdown') #13 [internal function]: shutdown_action_hook() #14 {main} thrown in C:\XAMPP\htdocs\wp-content\plugins\complianz-gdpr\functions.php on line 1873